BX280-AX

Modular gas detection ATEX controller: 2 conventional sensors

II (2) G EN 60079-29-1

Through the connection of 2 remote sensors, the BX280-AX control unit has been designed and built to detect the presence of toxic and/or explosive gas in a flexible way A microprocessor is used to create a complete surveillance and control system with maximum flexibility. Thanks to this and its other features, the BX280-AX is suitable for civil and industrial applications.

The BX280-AX control unit has two hazard levels:

1st LEVEL, 1st Pre-Alarm. It’s set at 13 % of L.E.L. for all sensors.

2nd LEVEL, Main Alarm. It’s set at 20% of L.E.L..

Main power supply: 110÷240 VCA 50/60 Hz

Secondary power supply: 12 V. dc ± 10%

Power demand: 6 W in alarm

Prealarm output relay: ON-OFF

Alarm output relay: in change 10A 250VAC

Fault relay:  ON-OFF

Conventional gas sensor: Max. 2

Catalytic, Electrochemical, Semiconductor, Pellistore

Explosive alarm threshold: 8 -13 – 20% LIE

Toxic alarm threshold: 120 – 200 – 300 ppm

Input signal: 4 ÷ 20 mA on 220 Ohm

Accuracy: 1% FS

Positive Security: Selectable

OVER LOAD control: 1 for each probe

OVER LOAD control: 1 per battery

Working temperature: -10 ° C ÷ + 60 ° C

Protection degree: P20 in air

Installation: Rail DIN/Omega bar

Dimensions: 105x90x58 6 modules

Package Dimensions: 100x130x95

Weight: 280 grams approx.

The perfect partner for the wholesaler

For years, Beinat is your company’s trusted partner: its products are 100% guaranteed and its reliability allows a constant turnover within your warehouse. The study of our products allows obtaining advanced equipment capable to meet all needs. Our quality certifications and warranty

CONTACT US

Our quality and guarantee certifications

The importance of quality policy

The goal has always been to provide products that meet the customer’s needs, through continuous performance improvement and with a full commitment.