BX280-AX
Modular gas detection ATEX controller: 2 conventional sensors
II (2) G EN 60079-29-1
Through the connection of 2 remote sensors, the BX280-AX control unit has been designed and built to detect the presence of toxic and/or explosive gas in a flexible way A microprocessor is used to create a complete surveillance and control system with maximum flexibility. Thanks to this and its other features, the BX280-AX is suitable for civil and industrial applications.
The BX280-AX control unit has two hazard levels:
1st LEVEL, 1st Pre-Alarm. It’s set at 13 % of L.E.L. for all sensors.
2nd LEVEL, Main Alarm. It’s set at 20% of L.E.L..
Main power supply: 110÷240 VCA 50/60 Hz
Secondary power supply: 12 V. dc ± 10%
Power demand: 6 W in alarm
Prealarm output relay: ON-OFF
Alarm output relay: in change 10A 250VAC
Fault relay: ON-OFF
Conventional gas sensor: Max. 2
Catalytic, Electrochemical, Semiconductor, Pellistore
Explosive alarm threshold: 8 -13 – 20% LIE
Toxic alarm threshold: 120 – 200 – 300 ppm
Input signal: 4 ÷ 20 mA on 220 Ohm
Accuracy: 1% FS
Positive Security: Selectable
OVER LOAD control: 1 for each probe
OVER LOAD control: 1 per battery
Working temperature: -10 ° C ÷ + 60 ° C
Protection degree: P20 in air
Installation: Rail DIN/Omega bar
Dimensions: 105x90x58 6 modules
Package Dimensions: 100x130x95
Weight: 280 grams approx.
The perfect partner for the wholesaler
For years, Beinat is your company’s trusted partner: its products are 100% guaranteed and its reliability allows a constant turnover within your warehouse. The study of our products allows obtaining advanced equipment capable to meet all needs. Our quality certifications and warranty
Our quality and guarantee certifications
The importance of quality policy
The goal has always been to provide products that meet the customer’s needs, through continuous performance improvement and with a full commitment.